24KV SF6 Insulated Ring Main Unit
Description
Unit
GLX24-K
GLX24-T
CLX24-V1/V2
CLX24-B
Rated voltage
KV
24
24
24
24
Power frequency withstand voltage(1min)
Phase to phase/earth
KV
50, (65)*
50, (65)*
50, (65)*
50, (65)*
Between open contacts
KV
64,(79)*
64,(79)*
64,(79)*
64,(79)*
Impulse withstand voltage
Phase to phase/earth
KV
95,(125)*
95,(125)*
95,(125)*
95,(125)*
Between open contacts
KV
110, (145)*
110, (145)*
110, (145)*
110, (145)*
Rated frequency
HZ
50, 60
50, 60
50, 60
50, 60
Rated current
A
630
①
630
630
Rated short circuit breaking current
KA
②
20
Rated short time withstand current
KA/s
20/3,(20/4)*
20/3,(20/4)*
20/3,(20/4)*
Rated peak withstand current
KA
50
50
50
Rated short circuit making current
KA
50
②
50
50
Rated transfer current
A
1400
Rated active load breaking current
A
630
630
Rated closed loop breaking current
A
630
630
5% rated active load breaking current
A
31.5
31.5
Rated operating sequence
0~0.3s~co~~co~
180s~c0
Mechanical lifetime
Ops.
5000
5000
10000
5000
Electrical lifetime
E3
E2
E3
Thickness of stainless steel
mm
3.0
SF6 rated pressure
kPa
30(at 20℃, 101.3kPa)
Leakage rate per year
≤0.02%
Water treatment test
24KV 24hours (at 30 kPa under water)
Internal Arc Test
20KA 1s
Protection Degree
Gas tank
IP67
Fuse holder
IP67
RMU
IP4X
These series Ring Main Unit is extensible, SF6 insulated switchgear, with reated voltage of 12&24KV. All its HV live parts are contained in an air-tight gas tank, which is made from stainless steel of 3mm. The whole switching assembly is SF6 insulated, any free from any external influence, ensuring it great reliability of service and maintenance free. By plug-in type busbar extension, the series RMU can be of free combination and full modularization. The busbar extension has passed type test for power and thermal stability, and is fully insulated and shielded, exhibiting high reliability and safety.
The series Ring Main Unit is suitable for all MV network up tp 24KV, all compact power stations, power distribution substations in all important industries, such as petrol-chemical industry, metallurgical and mining industries, and all transformer substations and wind power system.
Technical Date for 24KV Ring Main Unit
Notes:
①Rated current of Switch-fuse panel depends on rating of fuse, and ≤100A.
② Rated short-circuit breaking/making current of Switch-fuse panel depends on rating o fuse.
*Value in brackets are for special requirement, please contact us for more information. If 20KA/4s is required for rated short time withstand, please specify definitely when you are ordering.
- 24KV RMU 24KV Ring Main Unit power distribution substations i transformer substations wind power system.